Diesel Powered Generator
Standby Power
This rating is applicable for supplying Continuous Electrical Power (At a varying Load) in the event of a utility failure. No overload is permitted
Prime Power
This rating is applicable for supplying Continuous Electrical Power (at a varying load) in lieu of commercially purchased power. There is no limitation on the annual usage in terms of hours and an overload of 10% is available for every 1hr in 12hrs operation
CAT Powered Diesel Product Range - 50HZ
|
| |
|
|
|
|
|
|
|
| |
|
Standby
Rating
|
Prime
Rating
|
Fuel Con's
Ltrs/Hr
|
|
| |
|
KVA
|
KWe
|
KVA
|
KW
|
100% Load
|
|
| |
YPL-13.5-D |
13.5
|
11
|
12
|
10
|
3.2
|
|
| |
YPL-18-D |
18
|
14
|
16
|
13
|
4.3
|
|
| |
YPL-22-D |
22
|
18
|
20
|
16
|
5.7
|
|
| |
YPL-30-D |
30
|
24
|
27
|
22
|
8.5
|
|
| |
YPL-44-D |
44
|
35
|
40
|
32
|
10.9
|
|
| |
YPL-50-D |
50
|
40
|
45
|
36
|
13.09
|
|
| |
YPL-65-D |
65
|
52
|
60
|
48
|
15.7
|
|
| |
YPL-88-D |
88
|
70.4
|
80
|
64
|
19.7
|
|
| |
YPL-110-D |
110
|
88
|
100
|
80
|
26.6
|
|
| |
YPL-150-D |
150
|
120
|
135
|
108
|
31.2
|
|
| |
YPL-165-D |
165
|
132
|
150
|
120
|
41.1
|
|
| |
YPL-220-D |
220
|
176
|
200
|
160
|
47.2
|
|
| |
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| |
|
Standby
Rating
|
Prime
Rating
|
Fuel Con's
Ltrs/Hr
|
|
| |
|
KVA
|
KWe
|
KVA
|
KW
|
100% Load
|
|
| |
YPL-250-D |
250
|
200
|
230
|
184
|
53.3
|
|
| |
YPL-275-D |
275
|
220
|
250
|
200
|
60.1
|
|
| |
YPL-400-D |
400
|
320
|
N/A
|
N/A
|
85
|
|
| |
YPL-450-D |
450
|
360
|
N/A
|
N/A
|
89.1
|
|
| |
YPL-500-D |
500
|
400
|
450
|
360
|
99.9
|
|
| |
YPL-550-D |
550
|
440
|
500
|
400
|
121.4
|
|
| |
YPL-600-D |
600
|
480
|
540
|
432
|
123
|
|
| |
YPL-650-D |
650
|
520
|
585
|
468
|
133
|
|
| |
YPL-700-D |
700
|
560
|
630
|
504
|
146
|
|
| |
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| |
|
Standby
Rating
|
Prime
Rating
|
Fuel Con's
Ltrs/Hr
|
|
| |
|
KVA
|
KWe
|
KVA
|
KW
|
100% Load
|
|
| |
YPL-750-D |
750
|
600
|
675
|
540
|
158.9
|
|
| |
YPL-800-D |
800
|
640
|
720
|
576
|
169.1
|
|
| |
YPL-900-D |
900
|
720
|
810
|
648
|
191.7
|
|
| |
YPL-1000-D |
1000
|
800
|
900
|
720
|
216.5
|
|
| |
YPL-1100-D |
1100
|
880
|
990
|
792
|
227
|
|
| |
YPL-1250-D |
1250
|
1000
|
1125
|
900
|
267.4
|
|
| |
YPL-1400-D |
1400
|
1120
|
1260
|
1008
|
310.4
|
|
| |
YPL-1500-D |
1500
|
1200
|
1350
|
1080
|
338
|
|
| |
YPL-1600-D |
1600
|
1280
|
1440
|
1152
|
333.3
|
|
| |
YPL-1750-D |
1750
|
1400
|
1575
|
1260
|
370.4
|
|
| |
YPL-1875-D |
1875
|
1500
|
1688
|
1350
|
409
|
|
| |
YPL-2000-D |
2000
|
1600
|
1800
|
1440
|
420.9
|
|
| |
YPL-2250-D |
2250
|
1800
|
2025
|
1620
|
457.5
|
|
| |
YPL-2500-D |
2500
|
2000
|
2250
|
1800
|
547
|
|
| |
YPL-3000-D* |
3000
|
2400
|
2700
|
2160
|
599.4
|
|
Click here to request information on diesel powered generators
* Size and weight for this generator is approximate and excludes the radiator
All ratings are based on 1500RPM/50Hz and 380-415 Volt output (1800RPM/60Hz are available please contact the Sales Team)
Yellow Power Limited reserve the right to amend or change the above data without prior notification
|